SGB DL 280 8S Pressure Leak Detector – 230 VAC, Plastic Housing (QU8/6)
The DL 280 8S is an advanced pressure leak detector designed to monitor double-walled underground tanks for water-polluting liquids—including fuels and solvents. It operates by maintaining overpressure in the interstitial space, triggering both visual and audible alarms on pressure drops. The “8S” variant adds integrated monitoring of up to eight sumps or ancillary chambers via leak sensors (sold separately).
Product Specifications
| Attribute | Details |
| Model | DL 280 8S |
| Alarm Pressure | Approx. 280 mbar |
| Test Pressure Required | Minimum 400 mbar in interstitial space |
| Tank Diameter | Up to 2.5 m (underground double-walled tanks) |
| Additional Monitoring | Supports simultaneous monitoring of up to 8 sumps/chambers (via Ex-floating sensors) |
| Power Supply | 230 VAC, 50 Hz |
| Housing | Plastic box (IP30) |
| Temperature Range | 0 °C to +40 °C (indoor only) |
| Connection | Quick union QU8/6 (for 8 mm × 6 mm polyamide hose) |
| Applications | Monitoring of water-polluting or potentially flammable liquids (gas groups IIA–IIB3, temp class T1–T3) |