VEGAMET 842 Controller for two 4-20mA sensor input (With ATEX intrinsically safe sensor supply)

Monitoring & Control

Stock Code: CR - 222 232

£715.00
Buy Now

2 x 4-20 mA sensor inputs, 2 x 4-20 mA current outputs, 3 x operating relay (1 of which can be used as a fail-safe relay).

ATEX/UKEX approved for installation in an Ex-free area but with intrinsically safe sensor supply. Appropriate sensor can be installed Zone 0, 1, 2 (Class I Division 1, 2)

The VEGAMET 842 controller feeds up to 2 x connected 4- 20 mA sensors, processes the measured values and displays them.

A large display for data visualisation is integrated in the housing designed for rough field conditions.

With a VEGAMET 842, tank level readings in one or two tanks can be reliably monitored and displayed as level, volume and/or percentage full, when used on a single tank Ullage can also be displayed in litres, and 1amp relays can be switched based on tank levels, e.g. for overfill protection alarm activation or pump/valve activation.

Integrated Bluetooth technology means the controller can be programmed, commissioned and troubleshooted quickly and easily via the free VEGATOOLS smartphone/tablet app or using a Bluetooth enabled PC with free VEGA software.

  • Input : 4-20mAmp x 2
  • Outputs: 2 x 0/4 … 20 mA current output, 3 x operating relay, 1x failure relay (instead of operating relay)
  • Ambient temperature: -40 to 60 °C
  • Operating voltage Ʋ Nominal voltage AC 100 … 230 V (-15 %, +10 %) 50/60 Hz Ʋ Nominal voltage DC 24 … 65 V (-15 %, +10 %) Power consumption max. 13 VA; 4 W
  • Type of input (selectable) Ʋ Active input Sensor supply through VEGAMET 841 Ʋ Passive input Sensor has an own voltage supply Measured value transmission Ʋ 4 … 20 mA analogue for 4 … 20 mA sensors
  • Relay output Quantity 3 x operating relay, one can be configured as fail safe relay Switching voltage max. 250 V AC/60 V DC Switching current max. 1 A AC (cos phi > 0.9), 1 A DC Breaking capacity min. 50 mW, max. 250 VA, max. 40 W DC (with U < 40 V DC)
  • Indicators Measured value indication Ʋ Graphic-capable LC display, with lighting 89 x 56 mm, digital and quasianalogue display
  • Ambient conditions Ambient temperature:
  • Ʋ Instrument in general -40 … +60 °C (-40 … +140 °F)
  • Ʋ Display (readability) -20 … +60 °C (-4 … +140 °F)
  • Electrical protective measures:
  • Protection rating IP66/IP67 acc. to IEC 60529, Type 4X acc. to UL 50

Protection rating :IP66/IP67, Type 4X Input :2 x 4 … 20 mA sensor input Output :2 x 0/4 … 20 mA current output 3 x operating relay 1x failure relay (instead of operating relay) Ambient temperature : -40 ... 60 °C

Approvals ATEX / Europe IEC / worldwide c-UL-us UKEX

Adjustment On-site adjustment Smartphone / Tablet / PC via Bluetooth

Indication LCD matrix display, black and white Backlight with colour change acc. to status