A skid-mounted twin-pump set for transferring diesel in generator fuel systems and between storage tanks. This standard-head version uses two 0.37 kW self-priming pumps and is designed for a maximum stated flow of 50 L/min and maximum stated discharge head of 30 m.
The two pumps are connected to stainless-steel suction and discharge manifolds with isolating union ball valves and non-return valves. This three-phase version is intended for commercial and industrial installations with an appropriate three-phase electrical supply.
Key features
- Two 0.37 kW self-priming diesel-transfer pumps
- Three-phase, 50 Hz motors
- Maximum stated flow: 50 L/min
- Maximum stated discharge head: 30 m
- Stainless-steel suction and discharge manifolds
- Isolating union ball valves and non-return valves
- 1 1/2-inch BSP male manifold connections
- Mounted on a folded stainless-steel baseplate
- Drip tray and drip-tray liquid switch available as options
Typical applications
- Generator bulk-tank to day-tank transfer
- Transfer between diesel storage tanks
- Commercial and industrial diesel-transfer systems
Controls and installation
A compatible three-phase control panel is required to provide automatic duty/standby operation. Control panels, alarms and monitoring options are supplied separately unless included in the selected configuration.
This pump set is intended for internal installation inside a suitable weather-proof building, plant room or enclosure supplied by others. Final selection must be based on the required operating flow, system head, suction conditions and available electrical supply.
| PFS product code |
PTS-DS-D-S50-30-3P |
| Application |
Diesel fuel transfer |
| Pump arrangement |
Twin pump, arranged for duty/standby operation |
| Pump type |
Self-priming peripheral-impeller pump |
| Maximum stated flow |
50 L/min (3 m³/h) |
| Maximum stated discharge head |
30 m |
| Motor power |
2 × 0.37 kW |
| Electrical supply |
Three phase, 50 Hz - supply voltage to be confirmed |
| Maximum system pressure |
6 bar |
| Maximum stated self-priming lift |
Up to 9 m, subject to application review |
| Maximum stated diesel temperature |
+55°C |
| Manifold connections |
1 1/2-inch BSP male |
| Manifold material |
Stainless steel |
| Mounting |
Folded stainless-steel baseplate |
| Control panel |
Not included unless specified |
| Installation location |
Internal, within a suitable weather-proof building or enclosure supplied by others |
Performance note: Maximum flow and maximum discharge head are separate limits. The required operating point must be checked against the applicable pump curve.