SECU Tank QUATTRO GSM ATG : Up to 4 tanks + GSM-data

Monitoring & Control

Stock Code: HW000085

Call

SECU Tank QUATTRO GSM is an electronic level indicator for measuring up to 4 unpressurized tanks for liquid products, including data transmitter.

The integrated GSM modem is sending tank information worldwide, over all common mobile providers, such as levels and critical levels (mini-mum levels, incidents of burners, etc.)

The package contains:

Display unit with digital level indication Integrated GSM modem

The level is controlled through measurement of the hydrostatic pressure of the tank level. After input of the tank data into the display unit during the installation, the calculation of the measurement values is done automatically.

The best solution for:

  • Control of tank volumes
  • Transfer of tank contents and tank data (1 display indicator – up to 4 tanks)

Transfer of the data:

  • per SMS to a mobile phone or depending on the provider
  • to the data-bank "tankmonitoring.net“, for complete control of the site

Necessary for use with data-transfer:

It is possible to choose between prepaid-card or contract card. If prepaid card is used you need to make sure that there is always enough balance available. The SIM-Card is not part of the delivery and needs to be purchased separately.

Advantages and Equipment:

  • Indication of the measured levels on the display of the digital indicator in litres, percentage of tank volume (%) or in centimetres (indication of up to 4 tanks changes in automatic intervals)
  • Indication of the ullage
  • Menu language in German, English and French
  • Extension of the probe wire up to 180 m

Technical Data:

  • Supply Voltage: 230 V AC 50 Hz
  • Range of Measurement: up to 25 m – according to probe
  • Tank Connection: G 1, G 1 1/2 bzw. G 2  Protection Class: IP30 or IP65
  • Optional interfaces: for 4-20mA, 0-5V, M-Bus, H-Protocol
  • Event message: for example message for site incident
  • Potential free relays with open/close contact: max. 250 V AC / 3,5 A